Forklift Requirements; Hoisting Requirements - Huawei LUNA2000-200KWH-2H1 User Manual

Smart string ess
Hide thumbs Also See for LUNA2000-200KWH-2H1:
Table of Contents

Advertisement

LUNA2000-200KWH-2H1 Smart String ESS
User Manual

5.4 Forklift Requirements

5.5 Hoisting Requirements

Issue 03 (2023-03-30)
The foundation should sustain the total weight of the equipment (2.8 tons). If
the load-bearing capacity of the foundation does not meet the requirement, a
review is required.
The bottom of the excavated foundation must be compacted and flat.
After the foundation is excavated, prevent water from entering the
foundation. If water enters the foundation, excavate and refill the affected
parts.
The level tolerance between the foundation and the contact surface of the
cabinet must be less than or equal to 3 mm.
The foundation must be above the highest water level of the local area in
history and at least 300 mm above the ground.
Construct drainage facilities based on the local geological conditions and
municipal drainage requirements to ensure that no water will accumulate at
the equipment foundation. The foundation construction must meet the local
drainage requirements for the maximum historical rainfall. The drained water
must be disposed of in accordance with local laws and regulations.
Reserve trenches or cable inlets for the ESS during foundation construction.
The reserved holes on the foundation and the cable inlets at the bottom of
the equipment should be sealed.
The foundation diagram is for reference only and cannot be used as the final
construction drawing. The design specifications of the ESS foundation should
be reviewed based on the installation environment, geological features, and
seismic resistant requirements of the project site.
Do not move the ESS after battery packs are installed.
Before using a forklift, ensure that the forklift has a load bearing capacity of
at least 1 t.
It is recommended that the length of the tynes be greater than or equal to
1.2 m, the width be 80 cm to 160 cm, and the thickness be 25 cm to 70 cm.
Lifting height of a forklift: If the foundation is less than or equal to 0.3 m
high, the lifting height should be greater than or equal to 2 m. If the
foundation is greater than 0.3 m high, the lifting height should be increased
accordingly.
Before hoisting, ensure that the crane and hoisting ropes meet the load-
bearing requirements.
When installing or removing the hoisting equipment, do not drag it on the
cabinet to prevent scratches.
Do not hoist or move the ESS after battery packs are installed.
Copyright © Huawei Digital Power Technologies Co., Ltd.