Huawei LUNA2000-200KWH-2H1 User Manual page 166

Smart string ess
Hide thumbs Also See for LUNA2000-200KWH-2H1:
Table of Contents

Advertisement

LUNA2000-200KWH-2H1 Smart String ESS
User Manual
Alarm
Alarm
ID
Name
3826
Combus
tible
Gas
Alarm
3827
Ambient
Temper
ature
High
3828
Condens
ation
Risk
Issue 03 (2023-03-30)
Alarm
Possible Cause
Severit
y
Major
Cause ID = 1
1. The safety valve of
the lithium battery
is open, and
combustible gas is
leaked.
2. Lithium battery
thermal runaway
has occurred.
Major
Cause ID = 1
The ambient
temperature in the
battery cabin is too
high.
Minor
Cause ID = 1
Condensation risk
exists in the battery
cabin.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Suggestion
1. Remotely monitor the system for 30
minutes to check whether other
exceptions (such as abnormal
temperature, abnormal battery
voltage, abnormal battery
temperature, and exhaust fan startup)
occur. If yes, ensure that the ESS is
shut down. During remote monitoring,
do not approach the battery cabin or
open the cabin doors.
2. If no exception is found during the
remote monitoring, assign trained
personnel to the site and observe the
system for 30 minutes from a safe
distance. If there is smoke or fire,
remotely power off the system,
evacuate onsite personnel as soon as
possible, and call the fire emergency
service.
3. If no exception is found during remote
monitoring and onsite observation,
manually clear the alarm. If the alarm
clearance fails, contact your technical
support.
1. Check whether the air conditioners in
the battery cabin are faulty.
2. Check whether the doors of the
battery cabin are completely closed.
3. After the battery cabin temperature
and battery rack temperature drop to
below 58°C, manually clear the alarm.
If the alarm persists, contact your
technical support.
1. This alarm indicates that the cabin
needs to be dehumidified. Ensure that
the temperature control mode is set to
automatic.
2. If the alarm persists for more than 30
minutes, check whether the air
conditioner in the battery cabin is
normal and whether the cabin doors
are completely closed.
13 Alarm Reference