Alar
Alarm
m ID
Name
3030
Battery
Module
Fan Fault
Issue 03 (2023-03-30)
Severit
Possible Cause
y
Major
Cause ID = 1
1. The fan is short-
circuited.
2. The power supply is
insufficient.
3. The fan is faulty.
4. The fan is blocked.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Suggestion
1. Determine the positions of the input
and output circuit breakers of the
ESC and the DC output power switch
of the PSU corresponding to [ESR-
CabinetNo ESM-SlotNo].
2. Check whether the PSU output DC
switch for the fan is turned on. If not,
turn it on. If yes, turn it off and check
whether the 48 V power supply of
the battery pack is securely
connected.
3. Issue a hibernation command to the
ESR corresponding to the ESC, and
turn off the switch on the battery
side, the switch on the bus side, and
the DC output switch of the PSU.
Then wait for 5 minutes.
4. Replace the fan if it is damaged,
clear the foreign matter if there are
any, and rectify power supply failure
if any.
5. Turn on the DC output switch of the
PSU, the switch on the battery side,
and the switch on the bus side in
sequence, and issue a running
command.
6. If the alarm persists, contact the
vendor or technical support.