Alarm
Alarm
ID
Name
3804
AC SPD
Fault
3805
Air
Conditio
ner
Temper
ature
High
3806
Air
Conditio
ner
Temper
ature
Low
Issue 03 (2023-03-30)
Alarm
Possible Cause
Severit
y
Major
Cause ID = 1
The AC SPD is faulty.
Major
Cause ID = 1–13
The return air
temperature of [HVAC-
No] exceeds the high
temperature alarm
threshold.
Major
Cause ID = 1–13
The return air
temperature of [HVAC-
No] is below the low
temperature alarm
threshold.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Suggestion
1. Check whether the AC SPD signal
cable is loose.
2. Check whether the color of the AC
SPD indicator changes.
3. Replace the AC SPD.
1. Check that the high temperature
alarm threshold is set to a proper
value. The default value is 45°C.
2. If the preceding threshold is set to a
proper value and multiple air
conditioners report the alarm, shut
down the system and contact your
technical support.
3. If only one air conditioner reports the
alarm, check other alarms reported by
the air conditioner and rectify the
faults based on the troubleshooting
suggestions. If no other alarm is
generated, shut down the air
conditioner and contact your technical
support.
1. Check that the low temperature alarm
threshold is set to a proper value. The
default value is –30°C.
2. If the preceding threshold is set to a
proper value and multiple air
conditioners report the alarm, shut
down the system and contact your
technical support.
3. If only one air conditioner reports the
alarm, check other alarms reported by
the air conditioner and rectify the
faults based on the troubleshooting
suggestions. If no other alarm is
generated, shut down the air
conditioner and contact your technical
support.
13 Alarm Reference
151