Huawei LUNA2000-200KWH-2H1 User Manual page 76

Smart string ess
Hide thumbs Also See for LUNA2000-200KWH-2H1:
Table of Contents

Advertisement

LUNA2000-200KWH-2H1 Smart String ESS
User Manual
Do not select the sites that are not recommended by industry standards and
regulations, including but not limited to the following areas:
Issue 03 (2023-03-30)
There are 1-hour freestanding fire walls, extending 5 ft (1.5 m)
above and extending 5 ft (1.5 m) beyond the physical boundary of
the ESS installation.
Non-combustible exterior walls with no openings or combustible
overhangs are provided on the walls adjacent to the ESS and the fire
resistance rating of the exterior walls complies with 2-hour fire
resistance rating of ASTM E119 or UL 263.
The ESS and the site should be in an environment free from explosion risks.
Transportation to the site should be convenient and fire suppression facilities
should be reliable.
NO TE
● When installing, commissioning, and operating the ESS, ensure that at least two
gas fire extinguishers are provided near each unit to ensure fire safety.
● The distance between the exhaust device of an ESS and the heating and ventilation
vents, air intake vents of air conditioners, windows, doors, unloading platforms,
and fire sources of other buildings or facilities must be greater than 4.6 m.
● Reserve sockets for the water fire suppression system at the ESS site.
The site area must meet the requirements and there should be space for
capacity expansion.
The ESS should be installed more than 30 m away from the third-party
wireless communication facilities.
The site must be in a well-ventilated place.
The ESS cannot be installed in salt-affected or polluted areas because this will
cause corrosion. The ESS can be used in the following or better environments:
Outdoor environment more than 2000 m away from the coast. You are
advised not to use the ESS in an area 500 m to 2000 m away from the
coast. (If you need to use it, confirm with the vendor or the Company's
engineers.) Do not use the ESS in an area less than 500 m away from the
coast.
More than 1500–3000 m away from heavy pollution sources such as
smelteries, coal mines, and thermal power plants
More than 1000–2000 m away from medium pollution sources such as
chemical, rubber, and electroplating industries
More than 500–1000 m away from light pollution sources such as
packing houses, tanneries, boiler rooms, slaughterhouses, landfill sites,
and sewage treatment plants
NO TE
Reselect the site if the safety distance for a site cannot meet the requirements of relevant
national standards.
Areas with sources of strong vibration, loud noises, and strong
electromagnetic interference
Areas with dust, oil fumes, harmful gases, corrosive gases, etc.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Site Requirements
67

Advertisement

Table of Contents
loading

This manual is also suitable for:

Luna2000-200kwh-100kw-2h1

Table of Contents