User Manual
Procedure
Step 1 Choose Settings > Battery Control > Capacity Limit to set the capacity limit.
Figure 10-25 Setting capacity limit
Parameter
No control
Active
capacity limit
Apparent
capacity limit
----End
Active Capacity Limit
Parameter
Maximum
active
capacity
PV power
limit when
electricity
meter fails
PCS power
limit when
electricity
meter fails
Issue 03 (2023-03-30)
Description
If this parameter is set to No control, the capacity of the grid-
connection point is not limited. The inverter and Smart PCS run
according to the preset control policy.
If this parameter is set to Active capacity limit, the active
power of the grid-connection point for purchasing or feeding
power cannot exceed the preset capacity limit.
If this parameter is set to Apparent capacity limit, the apparent
power of the grid-connection point for purchasing or feeding
power cannot exceed the preset capacity limit.
Description
Set this parameter according to the charging capacity in the
demand contract of the power grid company. Once set, the
active power of the grid-connection point for purchasing or
feeding power cannot exceed the preset value.
Specifies the active power limit of the inverter when the feed-in
meter communication is abnormal. You can manually change
the active power percentage of the inverter as required.
Specifies the active power limit of the PCS when the feed-in
meter communication is abnormal. You can manually change
the active power percentage of the PCS as required.