LUNA2000-200KWH-2H1 Smart String ESS
User Manual
Issue 03 (2023-03-30)
–
The working mode is set to Maximum self-consumption.
Figure 10-17 Working mode
Parameter
Active power
threshold of
grid during
battery
discharge
Adjustment
deadband
Automatic
SOC
calibration
–
The working mode is set to TOU.
Figure 10-18 Working mode
Copyright © Huawei Digital Power Technologies Co., Ltd.
10 SmartLogger Web-based Deployment
Description
Control the maximum target grid power when the
grid-connection point has zero power.
Allowed fluctuation of the target grid power for the
grid-connection point
▪
Enable: Automatic SOC calibration is enabled. If the
total charge and discharge energy reaches the
threshold or the calibration function has not been
triggered for 30 days, the SOC automatic calibration
is performed. The SOC automatic calibration is
performed in battery racks. During calibration, the
cut-off SOC settings will be ineffective.
▪
Disable: Automatic SOC calibration is disabled.
138