3.4 Bypass Input Electrical Specifications

Table 3-6 Bypass input electrical specifications
Item
Bypass voltage
Bypass frequency
tolerance
Issue 23 (2024-03-15)
15 kVA
● 80–280 V AC, single-phase
(When the voltage is 80–
176 V AC, the load power
is linearly derated to
40%–100%.)
● 138–485 V AC, three-
phase (When the voltage
is 138–305 V AC, the load
power is linearly derated
to 40%–100%.)
> 0.99
< 200 W
Enabled
120–280 V AC
Minimum 1.5 times the UPS rated capacity
OVC Ⅱ
6 kVA
● Upper threshold: 10%, 15%, 20%, 25%, or 30% at 208 V
AC
● Upper threshold: 10%, 15%, 20%, or 25% at 220 V AC
● Upper threshold: 10%, 15%, or 20% at 230 V AC
● Upper threshold: 10% or 15% at 240 V AC
● Lower threshold: 10%, 20%, 30%, 40%, 50%, or 60%
Maximum ±6 Hz (configurable on the LCD)
Copyright © Huawei Digital Power Technologies Co., Ltd.
20 kVA
● 80–280 V AC, single-
phase (When the voltage
is 80–176 V AC, the load
power is linearly derated
to 40%–100%.)
● 138–485 V AC, three-
phase (When the voltage
is 138–305 V AC, the load
power is linearly derated
to 40%–100%.)
10 kVA
15 kVA
3 Technical Specifications
20 kVA
37