UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery)
Issue 23 (2024-03-15)
Figure 5-29 Bypass screen
Table 5-20 Bypass settings
Item
Description
Max.
Upper threshold for the
voltage
bypass voltage. When
the difference between
the bypass voltage and
the rated output voltage
exceeds this value, the
system determines that
the bypass voltage is
abnormal and that the
bypass is unavailable.
This parameter is
configurable only after
the inverter is shut
down.
Min.
Lower threshold for the
voltage
bypass voltage. When
the difference between
the bypass voltage and
the rated output voltage
is greater than this
value, the system
determines that the
bypass voltage is
abnormal and that the
bypass is unavailable.
This parameter is
configurable only after
the inverter is shut
down.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Default
Value Range
Value
15%
208 V: 10%, 15%,
20%, 25%, 30%
220 V (380 V in the
case of three-phase
output): 10%, 15%,
20%, 25%
230 V (400 V in the
case of three-phase
output): 10%, 15%,
20%
240 V (415 V in the
case of three-phase
output): 10%, 15%
20%
10%, 20%, 30%, 40%,
50%, 60%
5 Control Panel
89