Huawei UPS2000-G User Manual page 87

Lead-acid battery
Hide thumbs Also See for UPS2000-G:
Table of Contents

Advertisement

UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery)
Table 5-11 Parallel-System Load
Item
N+X Parallel-System
Sys. Sout_A/Sys. Sout_ B/
Sys. Sout_C
Sys. Pout_A/Sys. Pout_ B/
Sys. Pout_C
Sys. Load ratio_A/Sys.
Load ratio_B/Sys. Load
ratio_C
Environment Monitoring
Figure 5-16 Environment Monitoring screen
Table 5-12 Environment Monitoring
Item
Ambient temp.
Issue 23 (2024-03-15)
NO TE
System information is not displayed in single UPS mode.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
A parallel system is running. X (value range: 0–3)
indicates the number of redundant UPSs
(configurable on the LCD); N (value range: 1–4)
indicates the number of requisite UPSs (total
number of UPSs minus X). The total number of
UPSs is automatically identified by the system.
Output apparent power of each phase in the
parallel system (Sys. Sout is displayed when
single-phase output mode is set. The parameters
are not displayed in single UPS mode.)
Output active power of each phase in the parallel
system (Sys. Pout is displayed when single-phase
output mode is set. The parameters are not
displayed in single UPS mode.)
Load ratio of each phase in the parallel system
(Sys. Load ratio is displayed when single-phase
output mode is set. The parameters are not
displayed in single UPS mode.)
Description
Temperature detected by the ambient temperature
and humidity (T/H) sensor (used together with an
SNMP card; if the sensor is not connected, N/A is
displayed.)