UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery)
Context
A shallow discharge test method that tests the battery loop reliability and short-
time backup capacity after batteries are charged for a long time (60 days by
default, 30 days to 90 days configurable).
Before a shallow discharge test, ensure that the load rate is 0%–100% and the
load fluctuation does not exceed 10%.
Procedure
Step 1 Check the battery status for test start conditions.
1.
Issue 23 (2024-03-15)
F
Battery Shallow Discharge Test
NO TICE
On the Main Menu screen, choose Status and press
screen, locate Battery Status.
Figure F-1 Battery Status screen
Copyright © Huawei Digital Power Technologies Co., Ltd.
F Battery Shallow Discharge Test
. On the Status
169