Unpacking And Checking - Huawei UPS2000-G User Manual

Lead-acid battery
Hide thumbs Also See for UPS2000-G:
Table of Contents

Advertisement

UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery)
Model
Wiring
Termina
l
Output
20 kVA
Bypass
(three-phase
input
input three-
Mains
phase
input
output)
Battery
Output

4.1.4 Unpacking and Checking

Figure 4-6
Figure 4-6 Transportation safety requirements
Issue 23 (2024-03-15)
Numb
Rated
er of
Voltage
Phases
1
220 V
AC/230 V
AC/240 V AC
3
380 V
AC/400 V
AC/415 V AC
3
-
± 240 V DC
3
380 V
AC/400 V
AC/415 V AC
NO TE
● If customers purchase input and output power cables by themselves, use the cables that
comply with standards proposed by the Underwriters Laboratories (UL) or International
Electrotechnical Commission (IEC).
● Two power sources are not supported by the 15 kVA/20 kVA models with single-phase
input single-phase output.
shows the transportation safety requirements.
Copyright © Huawei Digital Power Technologies Co., Ltd.
External
Cable
Circuit
Cross-
Breaker
Sectional
Area
125 A/2 P
2
25 mm
(character
istic D)
63 A/4 P
2
10 mm
(character
istic D)
63 A/4P
2
16 mm
63 A/4 P
2
10 mm
(character
istic D)
4 Installation
Terminal
Torque
Type
for
Tighteni
ng Bolts
4.8 N·m
2
25 mm
M6 OT
terminal
2
2.8 N·m
10 mm
M6 OT
terminal
2
4.8 N·m
16 mm
M6 90°
OT
terminal
2
2.8 N·m
10 mm
M6 OT
terminal
59

Advertisement

Table of Contents
loading

Table of Contents