UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery)
H
Generated an Alarm to Normal Mode and
Procedure
Step 1 Press the INFO button to confirm that the alarm is generated for the bypass
power supply.
Step 2 Press the OK button for 5 seconds or enter the control screen to start the inverter.
Step 3 Verify that the alarm is cleared and the alarm tone disappears.
----End
Issue 23 (2024-03-15)
Transferring the UPS That Has
Copyright © Huawei Digital Power Technologies Co., Ltd.
H Transferring the UPS That Has Generated an
Alarm to Normal Mode and Clearing the Alarm
Clearing the Alarm Tone
Tone
175