Huawei UPS2000-G User Manual page 96

Lead-acid battery
Hide thumbs Also See for UPS2000-G:
Table of Contents

Advertisement

UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery)
Issue 23 (2024-03-15)
Item
Description
Frequency
Set the system output
level
frequency level. If this
parameter is set to
Automatic, the system
output frequency is 50
Hz when the power-on
bypass frequency ranges
from 40 Hz to 55 Hz,
and the system output
frequency is 60 Hz when
the power-on bypass
frequency ranges from
55 Hz to 70 Hz
(excluding 55 Hz). This
parameter is
configurable only after
the inverter is shut
down.
Volt. adj.
You can adjust the
coef.
inverter rated output
voltage. Press <cf
id="Bold">+</cf> or <cf
id="Bold">–</cf> to
increase or decrease the
output voltage.
Converter
Specifies whether to
mode
enable converter mode.
In converter mode, the
output voltage and
frequency are fixed to
the preset values. This
parameter is
configurable only after
the inverter is shut
down.
NOTICE
In converter mode, the
bypass output and the
maintenance bypass are
unavailable. If you shut
down the inverter, the UPS
stops supplying power to
loads.
Bypass screen
Copyright © Huawei Digital Power Technologies Co., Ltd.
Default Value
Value Range
50 Hz
50 Hz, 60 Hz,
Automatic
0%
±5%, ±4%, ±3%,
±2%, ±1%,0%
Disabled
Disabled, Enabled
5 Control Panel
88