UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery)
Figure 6-20 EPO cable connection in a parallel system
Issue 23 (2024-03-15)
NO TE
● For UPS2000-G-15KRTL-01/UPS2000-G-20KRTL-01, choose Settings > System
Parameters > Other Settings and set EPO Enable to Enable.
● Connect an external switch to the EPO port on the UPS. After you turn on the switch,
the UPS stops inverter output and does not transfer to bypass mode. Output terminals
completely power off, which meets the emergency power-off purpose.
● The external EPO switch (switch or dry contact signals controlled by a switch) is
provided by the customer.