Advertisement

UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery)
Issue 23 (2024-03-15)
Table 5-24 Other settings
Item
Description
Recovery
Delay time that the UPS takes in
delay time
transferring from battery mode to normal
mode when the mains recovers This
parameter is configurable only after the
inverter is shut down.
NOTE
If Recovery delay time(s) is set to 0S, the
actual recovery delay time is 1 second.
Maximum
Maximum number of bypass transfers
bypass
within 30 minutes When the number of
transfer
bypass transfers exceeds this value, the
times
UPS keeps running in bypass mode (in
ECO mode, the UPS keeps running in
inverter mode). This parameter is
configurable only after the inverter is
shut down.
NOTICE
Do not set the UPS to ECO mode when the UPS
connects to an isolated transformer.
Output
If an output transformer is connected, set
transform
the parameter to Enabled; otherwise, set it
er
to Disabled. This parameter is
configurable only after the inverter is
shut down.
NOTE
When connecting an isolation transformer to
the system output, connect the UPS output
load to the pL terminal and disable the power
segment function.
Generator
If the mains input voltage quality is good,
mode
Weak adaptability mode is
recommended. If the mains input voltage
is of average quality (for example, a high-
performance generator or a common
power grid is connected), Balance mode is
recommended. If the mains input voltage
quality is poor (for example, a common
generator is connected), Strong
adaptability mode is recommended. This
parameter is configurable only after the
inverter is shut down.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Control Panel
Defau
Value
lt
Range
Value
5s
0–900s
3
1–3
Disabl
Disabled,
ed
Enabled
Balan
Weak
ce
adaptabi
mode
lity
mode,
Balance
mode,
Strong
adaptabi
lity
mode
94