UPS2000-G-(6 kVA-10 kVA)
Quick Guide
0
Issue: 06
Part number: 31505542
Date: 2020-09-11
HUAWEI TECHNOLOGIES CO., LTD.

Advertisement

Table of Contents
loading

Summary of Contents for Huawei UPS2000-G Series

  • Page 1 UPS2000-G-(6 kVA-10 kVA) Quick Guide Issue: 06 Part number: 31505542 Date: 2020-09-11 HUAWEI TECHNOLOGIES CO., LTD.
  • Page 2 (8) Cover for optional card slot (9) CAN BATT.240VDC AC INPUT communications port (10) Parallel port AC INPUT AC OUTPUT (11) Output sockets (12) AC input and output terminal cover 10 9 UG06009965 Copyright © Huawei Technologies Co., Ltd. 2020. All rights reserved.
  • Page 3: Installing A Single Ups

    3. Only engineers certified by the manufacturer or its agents are allowed to perform UPS commissioning and maintenance. Otherwise, personal injury or equipment damage may occur, and the resulting UPS faults are beyond the warranty scope of Huawei. Installing the UPS...
  • Page 4 OFF to prevent operations with power applied. 3. If the input or output cable connection needs to be changed, contact Huawei technical support if you are not familiar with the operation. Do not power on the UPS directly.
  • Page 5: Installing Battery Cables

    10 kVA Three-Phase Input and M5 (8 PCS) Single-Phase Output 2.8 N· m Wiring Terminal AC INPUT AC OUTPUT External Circuit 63 A (the characteristics of Breaker Earth Leakage 100 mA Circuit Breaker Cable Cross- 10 mm² Mains loads sectional Area Terminal Type 10 mm²...
  • Page 6 (Optional) Installing Cables for Optional Cards RMS- 1. For details about how to install the dry contact card and Modbus card, see the RELAY01A User Manual RMS-MODBUS01A User Manual , respectively. 2. For details about how to install the SNMP card without a USB port (old version), see the RMS-SNMP01A V100R001 Installation Guide .
  • Page 7: Verifying The Installation

    UPS or inside the UPS. Powering On and Starting the UPS User interface (UI) snapshots shown in this document correspond to V100R001C10SPC600 and are for reference only. If any UI changes are made, contact Huawei technical support to obtain the latest snapshots. Symbol...
  • Page 8 Powering On the UPS Start Check that the UPS has passed all check items described in chapter 6 "Verifying the Installation." Turn on the external battery circuit breaker if any. No: Start the UPS in battery mode. Start the UPS in Press normal mode? Turn on UPS upstream AC input circuit breaker (K1) and...
  • Page 9 The following screens apply to the UPS started in normal mode. Scenario 1: Initial Startup Set the language (preset: English), system parameters, and battery parameters. HUAWEI Scenario 2: Non-initial Startup If this is not the initial startup and these parameters have been set before, the system uses the existing settings by default.
  • Page 10: Shutting Down The Ups

    Perform "startup operations": On the standby screen, hold down for about 5 seconds. Release the button when you hear a beep tone. The startup screen is displayed. If the UPS starts successfully, it enters the normal mode. After you ensure that the UPS runs properly, turn on the AC output circuit breaker (Q1) to start loads.
  • Page 11: Parallel System Operations

    Parallel System Operations This section describes how to install a 1+1 parallel system. Installing a Parallel System Scenario 1 Rack-mounting Scenario 2 Tower-mounting When you tower-mount UPSs, place devices Install devices from bottom to top, as shown in including UPSs horizontally to facilitate cable the figure.
  • Page 12 Scenario 1 Without PDU 6 kVA Single-Phase Input M4 (12 PCS) and Output 1.4 N· m UPS 2 Mains loads UPS 1 UG06009985 10 kVA Single-Phase Input and Output M5 (12 PCS) 2.8 N· m UPS 2 Short-circuit busbar Mains loads UPS 1 Short-circuit...
  • Page 13 10 kVA Three-Phase Input and M5 (16 PCS) Single-Phase Output 2.8 N· m UPS 2 Mains loads UPS 1 UG07009996 Scenario 2 With PDU PDC-0091V2ACIOA V100R001 For details about PDU cable connections, see the Quick Installation Guide 6 kVA Single-Phase Input M4 (12 PCS) and Output 1.4 N·...
  • Page 14 10 kVA Single-Phase M5 (12 PCS) Input and Output 2.8 N· m UPS 2 UPS 1 PDC-0091V2ACIOA UG07009995 10 kVA Three-Phase Input and Single-Phase Output M5 (16 PCS) 2.8 N· m UPS 2 UPS 1 PDC-0091V2ACIOA UG07009994...
  • Page 15 Installing Battery Cables UPSs in a parallel system cannot share battery strings or battery packs. External Battery Strings (2 ≤ ≤ 4) battery port UPS 1 battery port BATT.240VDC BATT.240VDC Battery 1 Battery 1 Battery 1 Battery 1 Ground Ground point point Battery 20...
  • Page 16 (Optional) Installing Cables for Optional Cards The methods for installing the SNMP card and dry contact card for a parallel system and for a single UPS are the same. See the single UPS part for details. The following shows how to install cables for the Modbus card.
  • Page 17 Verifying the Installation 1. Check each UPS in the parallel system by following instructions in chapter 6 "Verifying the Installation." 2. Check that parallel cables are connected properly, and that the output voltage of each UPS in the parallel system is the same. Powering On and Starting the Parallel System Do not start loads before the parallel system is started.
  • Page 18: Shutting Down The Parallel System

    3. If no alarm is displayed on the monitoring screen, continue with the subsequent operations. If an alarm is displayed, clear the alarm. 4. Check that the bypass input is normal and the UPS has transferred to bypass mode by viewing the system running status on the LCD.
  • Page 19: Alarm Handling

    Alarm Handling UPS2000-G-(6 kVA-20 kVA) User Manual For more alarm handling, see the Alarm Alarm ID Alarm Alarm Impact on the Repair Proposal Name (Alarm ID- Severity Clear System Alarm Mode Cause) Abnormal 0001-01 Minor Automati • The UPS Possible causes: mains volt.
  • Page 20 Check battery parameter settings. • Check the charger. When batteries • are disconnected, check whether the charger voltage is normal. If the charge voltage exceeds the upper threshold, contact Huawei technical support. Batt. 0026-01 Minor Automati An alarm is Possible cause: The mains input is undervolt.
  • Page 21 The UPS may Measure: Rectify output port short transfer to circuits, power-on and restart the UPS. another working If the alarm persists, contact Huawei mode or shut technical support for repair. down. 0158-01 Minor Automatic If the bypass is...