Huawei UPS2000-G User Manual page 130

Lead-acid battery
Hide thumbs Also See for UPS2000-G:
Table of Contents

Advertisement

UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery)
Issue 23 (2024-03-15)
NO TICE
1. A 15 kVA/20 kVA long backup time UPS requires serial connection
of two battery packs in each group. A maximum of four groups
with eight battery packs can be connected in parallel. If more
than two battery packs need to be connected to the 15 kVA/20
kVA UPS with long backup time, the battery packs should be
connected in parallel and then connected to the battery input
ports of the UPS, as shown in the following figure. Connect
battery packs 1 and 2 in series, battery packs 3 and 4 in series,
battery packs 5 and 6 in series, and battery packs 7 and 8 in
series. Connect battery packs 1, 3, 5, and 7 in parallel and battery
packs 2, 4, 6, and 8 in parallel.
2. When battery packs are connected in series or parallel, only
battery packs of the same model and specifications can be
installed or replaced. Do not use battery packs of different models
or specifications together. For details, see the battery pack
nameplate.
3. Connect the 15 kVA/20 kVA UPS batteries to the UPS battery
ports. One UPS battery port can have only one OT terminal
installed. After connecting cables, install the UPS battery port
cover.
4. For more information, see
Quick Installation Guide and ESS-240V12-(9AhBPVBA04,
7AhBPVBA04) Battery Pack Quick Guide .
Copyright © Huawei Digital Power Technologies Co., Ltd.
ESS-240V12-(9AhBPVBA, 7AhBPVBA)
6 Operations
122