Huawei UPS2000-G User Manual page 115

Lead-acid battery
Hide thumbs Also See for UPS2000-G:
Table of Contents

Advertisement

UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery)
Issue 23 (2024-03-15)
Figure 5-41 Shallow Discharge screen (UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01)
Table 5-35 Shallow Discharge screen (UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01)
Item
Description
Timed
Specifies whether to enable the scheduled
shallow
shallow discharge test. If this parameter is
discharg
set to Enable, the system automatically
e test
performs a shallow discharge test when
the test interval arrives and the system
meets the shallow discharge conditions.
The parameter is configurable in any
mode.
Time
Set the interval for shallow discharge
interval
tests. The parameter is configurable in
any mode.
Discharg
Specifies the proportion of the discharge
e ratio
capacity to the total discharge capacity.
The parameter is configurable in any
mode.
Figure 5-42 Shallow Discharge screen (UPS2000-G-6KRTS/UPS2000-
G-10KRTS/UPS2000-G-15KRTL/UPS2000-G-20KRTL)
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Control Panel
Default
Valu
Value
e
Rang
e
Disabled
Disab
led,
Enabl
ed
60 days
30–
90
days
20%
10%–
50%
107