UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery)
Step 3 Start the shallow discharge test: Partially discharge the batteries. After all required
conditions are met, the test command is successfully delivered and the LCD
displays a Succeeded message.
Figure F-4 Shallow Discharge Test screen
If the shallow discharge test command is successfully executed, the charger
disables its output and the system is in battery mode. You can view the battery
information on the default screen (energy flow diagram). The normal mode
indicator (green) turns off, and the battery mode indicator (yellow) turns on.
Step 4 Tap Stop Test to forcibly stop the battery shallow discharge test.
Figure F-5 Stop Test screen
----End
Issue 23 (2024-03-15)
Copyright © Huawei Digital Power Technologies Co., Ltd.
F Battery Shallow Discharge Test
171