UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery)
5.6.3.5 Restoring Factory Settings
You can restore factory settings after the inverter shuts down.
5.6.4 Control
On the Main Menu screen, select Control, and press
displayed.
Startup
The Startup menu allows you to start the inverter.
Figure 5-43 Startup screen
Shutdown
The Shutdown menu allows you to shut down the inverter.
Issue 23 (2024-03-15)
Table 5-36 Shallow Discharge screen (UPS2000-G-6KRTS/UPS2000-
G-10KRTS/UPS2000-G-15KRTL/UPS2000-G-20KRTL)
Item
Description
Test
Specifies whether to periodically send
notificati
shallow discharge notifications. The
on
options are Disabled and Enabled. The
default value is Disabled. If the value is
set to Enabled, the system sends shallow
discharge test notifications at specified
intervals. The parameter is configurable
in any mode.
Time
Specifies the time interval for shallow
interval
discharge tests. The parameter is
configurable in any mode.
Discharg
Specifies the proportion of the discharge
e ratio
capacity to the total discharge capacity.
The parameter is configurable in any
mode.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Control Panel
Default
Valu
Value
e
Rang
e
Disabled
Disa
bled,
Enab
led
60 days
30–
90
days
20%
10%
–
50%
. The Control screen is
108