Item
Description
Intelli.
When it is set to Enabled,
Hibernatio
the intelligent battery
n
hibernation function is
enabled. The parameter is
configurable in any mode.
Over
Specifies an alarm threshold
temp.
for battery overtemperature.
thres.
The parameter is
configurable in any mode.
Under
Specifies an alarm threshold
temp.
for battery
thres.
undertemperature. The
parameter is configurable
in any mode.
Over
Set an alarm threshold for
current
battery overcurrent. The
thres.
parameter is configurable
in any mode.
Note: The overcurrent alarm
threshold can be set only
for the UPS2000-G-15
kVA/20 kVA.
Equalized Charge
Figure 5-36 Equalized Charge screen (UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01)
Table 5-27 Equalized Charge screen (UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01)
Item
Description
Equalized
Specifies whether to enable
charging
battery equalized charging.
The parameter is
configurable in any mode.
Time
Set the interval for equalized
interval
charging. The parameter is
configurable in any mode.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Control Panel
Default Value
Value Range
Disabled
Disabled,
Enabled
50°C
45–55°C
–5°C
–30°C to +5°C
Standard
Standard
backup time
backup time
model: 3.0 A
model: 2.0–4.0
A
Long backup
time model:
Long backup
6.0 A
time model:
4.0–8.0 A
Default
Value Range
Value
Enabled
Disabled,
Enabled
60 days
30–180 days