Huawei UPS2000-G User Manual page 114

Lead-acid battery
Hide thumbs Also See for UPS2000-G:
Table of Contents

Advertisement

UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery)
Issue 23 (2024-03-15)
Table 5-32 EOD settings – backup time first
Expected
≤ 0.1 CA
Backup
Time
Low
1.85
voltage
warning
threshold
(V/cell)
EOD
1.75
threshold
(V/cell)
Table 5-33 EOD settings – batt. protect first
Expected
≤ 0.1 CA
Backup
Time
Low
1.90
voltage
warning
threshold
(V/cell)
EOD
1.85
threshold
(V/cell)
Table 5-34 EOD settings – balanced mode
Expected
≤ 0.1 CA
Backup
Time
Low
1.85
voltage
warning
threshold
(V/cell)
EOD
1.80
threshold
(V/cell)
Shallow Discharge screen
Copyright © Huawei Digital Power Technologies Co., Ltd.
0.1CA–
0.5CA–
0.5CA
1CA
1.85
1.85
1.67
1.60
0.1CA–
0.5CA–
0.5CA
1CA
1.90
1.90
1.85
1.83
0.1CA–
0.5CA–
0.5CA
1CA
1.85
1.85
1.75
1.70
5 Control Panel
1CA–3CA
> 3 CA
1.85
1.85
1.60
1.60
1CA–3CA
> 3 CA
1.90
1.90
1.75
1.67
1CA–3CA
> 3 CA
1.85
1.85
1.67
1.65
106