Huawei UPS2000-G User Manual page 108

Lead-acid battery
Hide thumbs Also See for UPS2000-G:
Table of Contents

Advertisement

UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery)
Issue 23 (2024-03-15)
Item
Description
Voltage
Specifies the battery
equalized charging voltage.
The parameter is
configurable in any mode.
Max. time
Specifies the maximum
equalized charging time. The
parameter is configurable
in any mode.
Figure 5-37 Equalized Charge screen (UPS2000-G-6KRTS/UPS2000-
G-10KRTS/UPS2000-G-15KRTL/UPS2000-G-20KRTL)
Table 5-28 Equalized Charge screen (UPS2000-G-6KRTS/UPS2000-
G-10KRTS/UPS2000-G-15KRTL/UPS2000-G-20KRTL)
Item
Description
Equalized
Specifies whether to enable
charging
battery equalized charging.
The parameter is
configurable in any mode.
Time
Set the interval for equalized
interval
charging. The parameter is
configurable in any mode.
Voltage
Specifies the battery
equalized charging voltage.
The parameter is
configurable in any mode.
Max.
Set the maximum equalized
current
charging current. The
parameter is configurable
in any mode.
Max. time
Specifies the maximum
equalized charging time. The
parameter is configurable
in any mode.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Control Panel
Default
Value Range
Value
2.35 V/cell
2.33–2.40 V/cell
960
600–999
minutes
minutes
Default
Value Range
Value
Enabled
Disabled,
Enabled
60 days
30–180 days
2.35 V/cell
2.33–2.40 V/cell
2.0 A
Standard
backup time
model: 1.0–2.0
A
Long backup
time model:
1.0–4.0 A
960
600–999
minutes
minutes
100