Huawei UPS2000-G User Manual page 168

Lead-acid battery
Hide thumbs Also See for UPS2000-G:
Table of Contents

Advertisement

UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery)
Mai
Second-
n
Level
Men
Menu
u
Issue 23 (2024-03-15)
Third-Level
Fourth-Level
Menu
Menu
Time interval
Voltage
Max. current
(UPS2000-
G-6KRTS/
UPS2000-
G-10KRTS/
UPS2000-
G-15KRTL/
UPS2000-
G-20KRTL)
Max. time
Float
Voltage
Charge
Temp. comp.
coef.
Discharge
Max. time
(configurable
in non-
battery
mode)
EOD mode
(configurable
in non-
battery
mode)
EOD auto-
start
(configurable
after the
inverter shuts
down)
Bat mode
shut delay
Shallow
Timed
Discharge
shallow
discharge test
(UPS2000-
G-15KRTL-01/
UPS2000-
G-20KRTL-01)
Copyright © Huawei Digital Power Technologies Co., Ltd.
Value Range
30–180 days
2.33–2.40 V/cell
1.0–2.0 A (standard
model)
1.0–4.0 A (long
backup time model)
600–999 minutes
2.25–2.30 V/cell
0.0–6.0 mV/(°C*cell)
0–24 hours
Batt. protect first,
Backup time first, and
Balanced mode
Enabled and Disabled
0–600 seconds
Enabled and Disabled
C LCD Menus and Parameters
Preset Value
60 days
2.35 V/cell
2.0 A
960 min
2.25 V/cell
3.3 mV/(°C x cell)
16 hours
Backup time first
Enabled
0s
Disabled
160