D2-04Trs Relay Output - Automation Direct DL205 Manual

Hide thumbs Also See for DL205:
Table of Contents

Advertisement

3–30
I/O Wiring and Specifications
Outputs per module
Commons per module
Output Points Consumed
Operating voltage
Output type
Peak voltage
AC frequency
ON voltage drop
Max load current (resistive)
Max load current (resistive)
Max leakage current
Typical Relay Life (Operations)
Voltage &
Type of Load
24 VDC Resistive
500K
24 VDC Solenoid
100K
110 VAC Resistive
500K
110 VAC Solenoid
200K
220 VAC Resistive
350K
220 VAC Solenoid
100K
At 24 VDC, solenoid (inductive) loads over 2A cannot be used.
At 110 VAC, solenoid (inductive) loads over 3A cannot be used.
At 220 VAC, solenoid (inductive) loads over 2A cannot be used.
5–30 VDC
5–240 VAC
L
L
L
L
DL205 Installation and I/O Manual, Rev. B
D2–04TRS Relay Output
4
4 (isolated)
8 (only 1st 4pts. are used)
5–30VDC / 5–240VAC
Relay, form A (SPST)
30VDC, 264VAC
47–63 Hz
0.72 VDC maximum
4A / point
4A / point
8A / module (resistive)
8A / module (resistive)
0.1mA @ 264VAC
Load Current
1A
2A
3A
200K
100K
40K
250K
150K
100K
50K
150K
100K
50K
NC
NC
C0
0
C1
1
C2
2
C3
3
Max inrush current
Minimum load
Base power required 5v
OFF to ON response
ON to OFF response
Terminal type
Status indicators
Weight
Fuses
Points
4
4A
50K
3
100K
2
1
50K
0
OUT
RELAY
0
1
2
3
D2–04TRS
5 240VAC
4A 50/60Hz
5-30VDC
10mA-4A
NC
NC
C0
0
L
C1
1
L
C2
2
L
C3
3
5–30 VDC
L
5–240 VAC
D2–04TRS
5A for < 10ms
10mA
250mA Max
10 ms
10 ms
Removable
Logic Side
2.8 oz. (80 g)
1 per point
6.3A slow blow, replaceable
6.3A slow blow, replaceable
Order D2–FUSE–3 (5 per pack)
Derating Chart
0
10
20
30
40
32
50
68
86
104
Ambient Temperature (°C/°F)
Internal module circuitry
OUTPUT
L
COM
Line
6.3A
2A / Pt.
3A / Pt.
4A / Pt.
50
55
°
C
122 131
°
F
To LED