D2-12Ta Ac Output - Automation Direct DL205 Manual

Hide thumbs Also See for DL205:
Table of Contents

Advertisement

Outputs per module
Output Points Consumed
Commons per module
Operating voltage
Output type
Peak voltage
AC frequency
ON voltage drop
ON voltage drop
Max load current
Max load current
Derating Chart
Points
12
300mA / Pt.
9
6
3
0
0
10
20
30
40
32
50
68
86
104
Ambient Temperature (°C/°F)
15–132 VAC
L
L
L
L
L
L
15–132 VAC
L
L
L
L
L
L
D2–12TA AC Output
12
16 (4 unused, see chart below)
2 (isolated)
15–132 VAC
SSR (Triac)
132 VAC
47 to 63 Hz
< l.5 VAC (> 50mA)
< l.5 VAC (> 50mA)
< 4.0 VAC (< 50mA)
< 4.0 VAC (< 50mA)
0.3A / point,
0.3A / point,
1.8A / common
1.8A / common
250mA / Pt.
OUT
A
0
1
2
50 55
C °
3
B
122 131
F °
D2–12TA
15-132VAC
CA
10mA-0.3A
50/60 Hz
0
4
CA
0
1
4
5
1
2
5
NC
2
3
3
NC
NC
CB
CB
0
0
4
4
1
5
1
2
5
2
3
NC
3
NC
D2–12TA
When the AB switch is in the A position,
the LEDs display the output status of the
module's first 8 output points. Positon B
displays the output status of the mod-
ule's second group of 8 output points.
I/O Wiring and Specifications
Max leakage current
Max inrush current
Minimum load
Base power required
OFF to ON response
ON to OFF response
Terminal type
Status indicators
Weight
Fuses
Addresses Used
Points
Used?
Yn+0
Yes
Yn+1
Yes
15-110
Yn+2
Yes
VAC
Yn+3
Yes
4
Yn+4
Yes
5
Yn+5
Yes
Yn+6
No
Yn+7
No
n is the starting address
Internal module circuitry
OUTPUT
L
COM
Line
3.15A
15–132
VAC
DL205 Installation and I/O Manual, Rev. B
3–29
2mA (132VAC, 60Hz)
10A for 10 ms
10 mA
350 mA Max
1 ms
1 ms +1/2 cycle
Removable
Logic Side
2.8 oz. (80 g)
(2) 1 per common
3.15A slow blow, replaceable
3.15A slow blow, replaceable
Order D2–FUSE–1 (5 per pack)
Points
Used?
Yn+10
Yes
Yn+11
Yes
Yn+12
Yes
Yn+13
Yes
Yn+14
Yes
Yn+15
Yes
Yn+16
No
Yn+17
No
Optical
Isolator
To LED

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DL205 and is the answer not in the manual?

Subscribe to Our Youtube Channel

Table of Contents