F2-04Ad-1 4 Channel 4-20Ma Analog Input - Automation Direct DL205 Manual

Hide thumbs Also See for DL205:
Table of Contents

Advertisement

3–36
I/O Wiring and Specifications
F2–04AD-1 4 Channel 4–20mA Analog Input
This module requires a 24VDC user power supply for operation. See the F2–04AD–1L if you want to use a12VDC supply.
Number of Channels
4, single ended (one common)
Input Ranges
4 to 20 mA current
Resolution
12 bit (1 in 4096)
Active Low-pass
–3 dB at 20Hz, 2 poles
Filtering
(–12 dB per octave)
250W "0.1%, ½W current input
Input Impedance
Absolute Maximum
–40 mA to +40 mA, current input
Ratings
Converter type
Successive approximation
Conversion Time
1 channel per scan minimum
(PLC update rate)
(D2–230 CPU)
4 channels per scan minimum
(D2–240 or D2–250 CPU)
"1 count (0.025% of full scale) maximum
Linearity Error
(End to End)
"1 count
Input Stability
"12 counts max., @ 20mA current input
Full Scale Calibration
Error (offset error not
included)
Offset Calibration Error "7 counts max., @ 4mA current input
One count in the specification table is equal to one least significant bit of the analog data value (1 in 4096).
NOTE 1: Shields should be grounded at the signal source
Typical User Wiring
See NOTE 1
+
CH1
4–wire
+
4–20mA
Transmitter
+
CH2
3–wire
+
4–20mA
Transmitter
CH3
2-wire
+
4–20mA
Transmitter
CH4
2-wire
+
4–20mA
Transmitter
More than one external power supply can be used provided all the power supply commons are connected.
A Series 217, 0.032A, fast-acting fuse is recommended for 4–20mA current loops.
If the power supply common of an external power supply is not connected to 0VDC on the
module, then the output of the external transmitter must be isolated. To avoid "ground loop"
errors, recommended 4–20mA transmitter types are:
2 or 3 wire:
Isolation between input signal and power supply.
DL205 Installation and I/O Manual, Rev. B
0 VDC
CH1-
CH2-
CH3-
CH4-
+
Optional
External
+
P/S
18–30VDC
Maximum inaccuracy
Accuracy vs.
Temperature
Recommended Fuse
Digital Inputs
Input points required
Power Budget
Requirement
External
Power Supply
Operating
Temperature
Storage Temperature
Relative Humidity
Environmental air
Vibration
Shock
Noise Immunity
Internal
Module
Wiring
+24 VDC
250W
CH1+
250W
CH2+
250W
CH3+
250W
CH4+
OV
4 wire:
Isolation between input signal, power supply, and 4–20mA output
".5% @ 77°F (25°C)
".65% 32 to 140°F (0 to 60_C)
"50 ppm/_C maximum full scale
(including max. offset change)
0.032 A, Series 217 fast-acting,
current inputs
16 (X) input points
12 binary data bits, 2 channel ID bits
50 mA maximum, 5 VDC
(supplied by base)
80 mA maximum, +18 to +30 VDC
32 to 140° F (0 to 60_ C)
–4 to 158° F (–20 to 70_ C)
5 to 95% (non-condensing)
No corrosive gases permitted
MIL STD 810C 514.2
MIL STD 810C 516.2
NEMA ICS3–304
IN
ANALOG
+5V
+15V
0V
–15V
F2–04AD–1
18-30VDC
80mA
A to D
ANALOG IN
Converter
4-20mA
0V
+24V
CH1–
CH1+
CH2–
CH2+
CH3–
CH3+
CH4–
CH4+
F2–04AD–1
4CH