Procedure
1. To zero the transmitter, first close the block valve on the low pressure (downstream)
Emerson.com
side of the transmitter.
A. High
B. Low
C. Test (plugged)
D. Equalize (closed)
E. Isolate (open)
F. Isolate (closed)
G. Process
H. Drain vent
NOTICE
Opening the low side equalize valve before the high side equalize valve will
overpressure the transmitter.
Do not open the low side equalize valve before the high side equalize valve.
Hardware installation