Emerson Rosemount 2051 Reference Manual page 101

Pressure transmitter with hart revision 5 and 7 selectable protocol
Hide thumbs Also See for Rosemount 2051:
Table of Contents

Advertisement

Reference Manual
00809-0100-4107
Recommended action
Replace the pressure transmitter.
Critical Sensor Data Error
LCD display
screen
Local operator
interface (LOI)
screen
A user-written parameter does not match the expected value.
Recommended actions
Critical Electronics Data Error
LCD display
screen
Local operator
interface (LOI)
screen
A user-written parameter does not match the expected value.
Recommended actions
Sensor Failure
LCD display
screen
Local operator
interface (LOI)
screen
A failure has been detected in the pressure sensor.
Recommended action
Replace pressure transmitter.
Incompatible Electronics and Sensor
LCD display
screen
Local operator
interface (LOI)
screen
The pressure sensor is incompatible with the attached electronics.
Emerson.com
MEMRY ERROR
MEMORY ERROR
1. Confirm and correct all parameters listed in Device Information.
2. Perform a device reset.
3. Replace pressure transmitter.
MEMRY ERROR
MEMORY ERROR
1. Confirm and correct all parameters listed in Device Information.
2. Perform a device reset.
3. Replace pressure transmitter.
FAIL SENSOR
FAIL SENSOR
XMTR MSMTCH
XMTR MSMTCH
Troubleshooting
February 2024
101