Reference Manual
00809-0100-4107
Alarm and saturation levels must be separated by at least 0.1 mA (0.025 Vdc)
The configuration tool will provide an error message if the configuration rule is violated.
Note
Transmitters set to HART
digitally; saturation and alarm conditions will not affect the analog output.
Related information
Move alarm switch
Establishing multidrop communication
Configure alarm and saturation levels using a communication
device
Procedure
From the HOME screen, enter the fast key sequence:
Fast keys
Configure alarm and saturation levels using AMS Device
Manager
Procedure
1. Right-click the device and select Configure.
2. Select Configure Alarm and Saturation Levels.
3. Follow screen prompts to configure alarm and saturation levels.
Configure alarm and saturation levels using a local operator
interface (LOI)
Procedure
Refer to
Figure 2-13: Configuring alarm and saturation using LOI
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
2.7.2 
Configuring scaled variable
With the scaled variable configuration, you can create a relationship/conversion between
the pressure units and user-defined/custom units. There are two use cases for a scaled
Emerson.com
multidrop mode send all saturation and alarm information
®
2, 2, 2, 5
Figure 2-13
to configure alarm and saturation levels.
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMULATE
HART REV
BACK TO MENU
EXIT MENU
Configuration
February 2024
ALARM SAT VALUES
ROSEMOUNT VALUES
NAMUR VALUES
OTHER VALUES
BACK TO MENU
EXIT MENU
25