Reference Manual
00809-0100-4107
Range = e - s to h + e -s
= 50 - 660 to 500 + 50 - 660
= -610 to - 110 inH
A. Zero elevation
Bubbler system in open vessel
You can use a bubbler system that has a top-mounted pressure transmitter in open
vessels. This system consists of an air supply, pressure regulator, constant flow meter,
pressure transmitter, and a tube that extends down into the vessel.
Bubble air through the tube at a constant flow rate. The pressure required to maintain flow
equals the liquid's specific gravity multiplied by the vertical height of the liquid above the
tube opening.
Emerson.com
O
2
Figure 3-23
shows a bubbler liquid level measurement example.
Hardware installation
February 2024
65