Emerson Rosemount 2051 Reference Manual page 20

Pressure transmitter with hart revision 5 and 7 selectable protocol
Hide thumbs Also See for Rosemount 2051:
Table of Contents

Advertisement

Configuration
February 2024
Rerange by manually setting range points with a communication device, AMS Device
Manager, or local operator interface (LOI).
Rerange with a pressure input source and a communication device, AMS Device
Manager, LOI, or local Zero and Span buttons.
Manually rerange the transmitter by entering range points
Enter range points using a communication device
Procedure
From the HOME screen, enter the fast key sequence:
2, 2, 2, 1
Enter range points using AMS Device Manager
Procedure
1. Right-click the device and select Configure.
2. Go to Manual Setup → Analog Output.
3. Enter upper and lower range values in the Range Limits box and select Send.
4. Carefully read the warning and select Yes if it is safe to apply the changes.
Enter range points using a local operator interface (LOI)
Procedure
See to rerange the transmitter using the LOI. Enter values using the SCROLL and ENTER
buttons.
Figure 2-8: Rerange using LOI
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
Reranging the transmitter with applied pressure source
Reranging using an applied pressure source is a way of reranging the transmitter without
entering specific 4 and 20 mA (1–5 Vdc) points.
Rerange with an applied pressure source using a communication
device
Procedure
From the HOME screen, enter the fast key sequence:
Fast keys
20
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT
VALUES
PASSWORD
SIMLATE
HART REV
BACK TO MENU
EXIT MENU
2, 2, 2, 2
Reference Manual
00809-0100-4107
TRANSFER FUNCT
LINEAR TRANSFER
FUNCTION
SQR ROOT TRANSFER
FUNCTION
BACK TO MENU
EXIT MENU
Rosemount 2051