3_Technical Characteristics; Plate Data - Tecnosystemi HI-TECH PUR 4.0 User Manual

Table of Contents

Advertisement

Available languages

Available languages

3_TECHNICAL CHARACTERISTICS

3.1 PLATE DATA

Airflow (m3/h)
Airflow (l/s)
External pressure (Pa)
ENTH. EFF. (%)
TEMP. EFF (%)
NOISE DB(A)
POWER SUPPLY
INPUT POWER (W)
POWER CABLE
CONTROL CABLE
STANDARD
CONTROL
FAN TYPE
FAN SPEEDS
SUMMER BYPASS
FAN BOOST CONTACTS
FIRE SHUTDOWN
WEIGHT (kg)
DUCT SIZE (mm)
ELECTRICAL AND PERFORMANCE DATA
ACD300002
250
70
100
COOLING
62-71
HEATING
65-73
73
34.5
80
(BMS)
MODBUS
Yes (1x available connections to Volt-Free contacts: Close= boost to High Speed)
Yes (1x available connection to Volt-Free contacts: Closed = Shutdown)
25
144
ACD300003
ACD300004
500
800
139
222
120
150
60-74
63-71
63-78
65-75
76
76
39
42
220-240V - 50Hz - 1Ph
230
368
3 x 1.5 mm2
2 x 0.5 mm2
Yes (7-Day Time-clock)
Yes
BLDC Fan Motors
10 Speed Fan Control
Yes (Automatic with adjustable range)
34
61
194
242
ACD300005
ACD300006
1000
1300
278
361
150
90
60-70
56-68
62-72
59-70
76
73
43
43
409
424
71
71
242
242
45