Printer Outlet Voltages-50 Hz - Xerox 4850 Installation Planning Manual

Xerox 4850: user guide
Hide thumbs Also See for 4850:
Table of Contents

Advertisement

Printer power cord
configurations
Single phase
DELTA
configurations
Installation Planning Guide
The following figure shows the 60 Hz power cord configuration
for
30 amp NEMA 14-30R. Voltage to ground is shown for
troubleshooting purposes.
Figure 6-1. 60 Hz power configuration
Printer outlet voltages—50 Hz
All power outlets must have a dedicated circuit for each system
equipment piece. Make sure each power cord has a separate
circuit.
50 Hz systems: Ensure that power connections are per local
codes/regulations.
For 50 Hz DELTA configurations, measure the DELTA connection
voltages at the power source.
Table 6-6. 50 Hz single phase DELTA outlet voltage
Wiring
Line to neutral
Neutral to ground
Printer specifications and requirements
requirements
Nominal
Range
220 VAC
198-242 VAC
230 VAC
207-253 VAC
240 VAC
216-264 VAC
0 VAC
<10 VAC
6-3