4 Designing the Power Supply System
Configuration Example
Iui1 + Iui2 + Iui3
Unit/input power supply
Output power supply
Iui1: Total current consumption of ILM1 from Unit/input power supply
Iui2: Total current consumption of ILM2 from Unit/input power supply
Iui3: Total current consumption of ILM3 from Unit/input power supply
Io1: Total current consumption of ILM1 from output power supply
Io2: Total current consumption of ILM2 from output power supply
Io3: Total current consumption of ILM3 from output power supply
Application Conditions for Connected External Devices
The conditions are the same as those in Calculation Example for the Total Current Consumption in
Direct Power Supply on page 4-9.
Calculating the Total Current Consumption
The total current consumption of each Unit is calculated as follows, according to Calculation Exam-
ple for the Total Current Consumption in Direct Power Supply on page 4-9.
a. Sum of the total current consumption of ILM1
(Total current consumption of ILM1 from Unit/input power supply) + (Total current consumption
of ILM1 from output power supply)
= (Iui1) + (Io1)
= (60 mA + 103.0 mA + 36.3 mA) + (100 mA + 2 A + 1 A)
≈ 3.30 A
b. Sum of the total current consumption of ILM2
(Total current consumption of ILM2 from Unit/input power supply) + (Total current consumption
of ILM2 from output power supply)
= (Iui2) + (Io2)
= (60 mA + 69.3 mA) + (100 mA + 2 A)
≈ 2.23 A
c. Sum of the total current consumption of ILM3
The formula is the same as that of ILM2.
(Total current consumption of ILM3 from Unit/input power supply) + (Total current consumption
of ILM3 from output power supply)
4-16
ILM1
ILM2
Io1
Io2
Iui1
Iui2
Iui3
Iui2 + Iui3
Io2 + Io3
Io1 + Io2 + Io3
ILM3
Io3