Event name
Device Configuration Verification Error
Meaning
The connected device is different from the IO-Link device registered for a port of the IO-Link Master.
Source
EtherCAT Master Function Mod-
ule
Error attrib-
Level
utes
Recovery
Effects
User program
System-de-
Variable
fined varia-
None
bles
Cause and
Assumed cause
correction
The connected device is different
from the IO-Link device regis-
tered for a port of the IO-Link
Master.
Attached in-
Attached information 1: Port where error occurred
formation
Precautions/
The emergency error code is FF2£ hex.
Remarks
Note £ represents port number 1 to 8.
NXR-series IO-Link Master Unit for EtherCAT User's Manual (W640)
Source details Slave
Minor fault
Reset error
Continues.
Operation
Data type
---
Correction
Connect the IO-Link device reg-
istered for the port of the IO-Link
Master.
1 hex: Port 1
2 hex: Port 2
3 hex: Port 3
4 hex: Port 4
5 hex: Port 5
6 hex: Port 6
7 hex: Port 7
8 hex: Port 8
11 Troubleshooting
Event code
847C0000 hex
Detection tim-
ing
Log category
System
Operation will continue.
In the port with the error, cyclic communications
with the IO-Link device are not correct.
Name
---
Prevention
Connect the IO-Link device reg-
istered for the port of the IO-Link
Master.
When an IO-
Link device is
connected
11
11-21