Omron NXR Series User Manual page 197

Environment-resistive remote terminal
Hide thumbs Also See for NXR Series:
Table of Contents

Advertisement

Accessing I/O Data in the IO-Link Master Unit
You can use this method to read the Output Power Supply Voltage Drop.
From the user program, etc., access the Output Power Supply Voltage Drop in the I/O Port Status of
I/O data.
Refer to 11-3 Checking for Errors with the Status in I/O Data on page 11-14 for information on Output
Power Supply Voltage Drop.
Reading Parameters through SDO Communications
You can use this method to read the Output Power Supply Voltage, Maximum Output Power Supply
Voltage, and Minimum Output Power Supply Voltage.
Read parameters from the following CoE objects through SDO communications.
Subin-
Index
dex
(hex)
(hex)
320E
---
Output Power Supply Voltage
Information
01
Output Power Supply Voltage
02
Maximum Output Power Sup-
ply Voltage
03
Minimum Output Power Sup-
ply Voltage
Refer to A-1-8 Manufacturer-specific Object 2 on page A-23 for information on CoE objects.
NXR-series IO-Link Master Unit for EtherCAT User's Manual (W640)
Size (Da-
Object name
ta type)
---
2 bytes
(U16)
2 bytes
(U16)
2 bytes
(U16)
Description
---
Indicates the present value of the output power supply
voltage. The unit is 0.1 V.
The default setting is 0.
Indicates the maximum value of the output power supply
voltage. The unit is 0.1 V.
The default setting is 0.
Indicates the minimum value of the output power supply
voltage. The unit is 0.1 V.
The default setting is 0.
9 Functions
9
9-27

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nxr-ilm08c-ect

Table of Contents