10 Setting Up IO-Link Devices
Storing the Parameters for an IO-Link Device
Precautions for Correct Use
• You cannot store the parameters in the IO-Link device if Cycle Read is set to Enable for
Dynamic variables or Process data in the Configuration tab page for the IO-Link device.
Set Cycle Read to Disable if you want to store the parameters in the IO-Link device.
• Do not disconnect the cable or turn OFF the power supply to the EtherCAT master or IO-Link
Master Unit when you store parameters from the CX-ConfiguratorFDT to an IO-Link device.
1
Go online with the IO-Link device. The operation differs depending on the version as follows.
• For the CX-ConfiguratorFDT version 3.0 or higher, right-click the device DTM for the IO-Link
device and select Connect.
• For the CX-ConfiguratorFDT version lower than 3.0, right-click the device DTM for the IO-
Link device and select Go online.
When the Support Software goes online, the following occurs depending on the version.
• For the CX-ConfiguratorFDT version 3.0 or higher, the status bar to the left of the devices in
the Network View turns green.
• For the CX-ConfiguratorFDT version lower than 3.0, the devices in the Network View are dis-
played in bold.
2
Right-click the device DTM again and select Store to device.
The parameter settings are stored in the IO-Link device.
Precautions for Correct Use
To change the parameters of IO-Link devices with the CX-ConfiguratorFDT, set the Port
Backup/Restore Setting for the port to Do Not Execute or Backup.
If you set the Port
automatically executes a restore operation when IO-Link device parameters are transferred with
the CX-ConfiguratorFDT. However, the data restored at this time is the data before the transfer.
You cannot change the parameter settings for IO-Link devices even if you transfer them with the
CX-ConfiguratorFDT.
Loading Parameter Settings from IO-Link Devices
Precautions for Correct Use
You cannot load the parameters from the IO-Link device if Cycle Read is set to Enable for
Dynamic variables or Process data in the Configuration tab page for the IO-Link device.
Set Cycle Read to Disable if you want to load the parameters from the IO-Link device.
1
Go online with the IO-Link device. The operation differs depending on the version as follows.
• For the CX-ConfiguratorFDT version 3.0 or higher, right-click the device DTM for the IO-Link
device and select Connect.
• For the CX-ConfiguratorFDT version lower than 3.0, right-click the device DTM for the IO-
Link device and select Go online.
When the Support Software goes online, the following occurs depending on the version.
10-14
£ Backup/Restore Setting for the port to Restore, the IO-Link Master Unit
NXR-series IO-Link Master Unit for EtherCAT User's Manual (W640)
£