Specifications - PROLiNK Professional II+ Series User Manual

Tower type
Hide thumbs Also See for Professional II+ Series:
Table of Contents

Advertisement

6. SPECIFICATIONS

TYPE
CAPACITY*
INPUT
Low Line Loss
Voltage
Low Line Comeback
Range
High Line Loss
High Line Comeback
Frequency Range
Phase
Power Factor
OUTPUT
Output voltage
AC Voltage Regulation
Frequency Range
(Synchronized Range)
Frequency Range (Batt. Mode)
AC mode
Overload
Battery mode
Current Crest Ratio
Harmonic Distortion
Transfer
Line
Time
Bypass Inverter
EFFICIENCY
AC mode
Battery Mode
BATTERY
Battery Type
Numbers
Standard
Recharge Time
Model
Charging Current
Charging Voltage
PHYSICAL
Standard
Dimension D*W*H(mm)
Model
Net Weight (kgs)
ENVIRONMENT
Operation Temperature
Operation Humidity
Operation Altitude**
Acoustic Noise Level
MANAGEMENT
Smart RS-232 or USB
Optional SNMP
* Lower capacity to 60% of capacity in CVCF mode and up to 90% when output voltage is adjusted to 208VAC.
** If the UPS is installed or used in places with altitudes above 1000m, the output power should be lowered by one percent per 100m.
Product specifications are subject to change without further notice.
Battery
(battery life cycle will be shorten when temperature is above 25°C)
Less than 55dB @ 1 Meter
Supports Windows 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, Unix,
INSPIRE 906-ES
6000 VA / 5400 W
110 VAC ± 3% at 50% Load;
176 VAC ± 3% at 100% Load
Low Line Loss Voltage + 10V
300 VAC ± 3 %
High Line Loss Voltage - 10V
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Single phase with ground
≧ 0.99 at 100% Load
208/220/230/240VAC
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
100% ~ 110%: 30min; 110% ~ 130%: 5min; > 130%: 10sec
100% ~ 110%: 3min; 110% ~ 130%: 30sec; > 130%: 10sec
≦ 3 % THD (Linear Load)
≦ 5 % THD (Non-linear Load)
> 92%
> 90%
16
9 hours recover to 90% capacity
Default : 1 A ± 10%
Max.: 1A, 2A (Adjustable)
218.4V ± 1%
369 x 190 x 688
61
<95 % and non-condensing
Power management from SNMP manager and web browser
21
INSPIRE 910-ES
10000 VA / 9000 W
± 1%
3:1 max
0 ms
0 ms
> 93%
> 91%
12 V / 9 Ah
16
218.4V ± 1%
442x 190 x 688
66
0 ~ 40°C
<1000m
Less than 58dB @ 1 Meter
and MAC

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Professional II+ Series and is the answer not in the manual?

Subscribe to Our Youtube Channel

This manual is also suitable for:

Inspire 906-esInspire 910-es

Table of Contents