6. SPECIFICATIONS

TYPE
CAPACITY*
INPUT
Low Line Loss
Low Line Comeback
Voltage
Range
High Line Loss
High Line Comeback
Frequency Range
Phase
Power Factor
OUTPUT
Phase
Output voltage
AC Voltage Regulation
Frequency Range
(Synchronized Range)
Frequency Range (Batt. Mode)
AC mode
Overload
Battery mode
Current Crest Ratio
Harmonic Distortion
Line
Battery
Transfer
Bypass Inverter
Time
ECO Inverter
EFFICIENCY
AC mode
ECO mode
Battery Mode
BATTERY
Type
Numbers
Standard
Recharge Time
Model
Charging Current (max)
Charging Voltage
Type
Numbers
Long-run
Model
Charging Current(max.)
Charging Voltage
PHYSICAL
Dimension, D X W X H mm
Standard
Model
Net Weight (kgs)
Dimension, D X W X H mm
Long-run
Model
Net Weight (kgs)
ENVIRONMENT
Operation Temperature
Operation Humidity
Operation Altitude**
Acoustic Noise Level
MANAGEMENT
Smart RS-232 or USB
Optional SNMP
* Lower capacity to 90% when output voltage is set to 208VAC.
**If the UPS is installed or used in places with altitudes above 1000m, the output power should be reduced by 1% per 100m.
Product specifications are subject to change without further notice.
INSPIRE 83330-QS
30KVA/30KW
110 VAC(Ph-N) ± 3 % at 50% Load; 176 VAC(Ph-N) ± 3 % at 100% Load
300 VAC(L-N) ± 3 % at 50% Load; 276 VAC(L-N) ± 3 % at 100% Load
46Hz ~ 54 Hz @ 50Hz system ; 56 Hz ~ 64 Hz @ 60Hz system
360/380/400/415VAC (Ph-Ph)
208*/220/230/240VAC (Ph-N)
46Hz ~ 54Hz @50Hz system;
56Hz ~ 64 Hz @ 60Hz system
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
100%~110%: 60min; 110%~125%: 10min; 125%~150%:1min;>150% : immediately
100%~110%: 60min; 110%~125%: 10min; 125%~150%:1min;>150% : immediately
≦ 1% @ 100% Linear Load; ≦ 3% @ 100% Non-linear Load
0 ms (When phase lock fails, <4ms interruption occurs from inverter to bypass)
12 V / 7 Ah
9 hours recover to 90% capacity
2.0 A ± 10% (Recommended) 1.0~16.0A (Adjustable)
+/- 13.65 VDC * N ± 1% (N = 16~20)
225
60
0 ~ 40°C (the battery life will down when > 25°C)
Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix, and MAC
Power management from SNMP manager and web browser
37
Low Line Loss Voltage + 10V
High Line Loss Voltage - 10V
3 Phase with Neutral
≧ 0.99 at 100% Load
3 Phase with Neutral
± 1%
3:1 max
0 ms
<10 ms
95.5%
98.5%
94.5%
(16+16)pcs x 2 strings
+/-218 VDC ± 1%
Depending on applications
32 ~ 40 (adjustable)
1.0~12.0A ±10% (Adjustable)
815 x 300 x 1000
815 x 300 x 1000
<95 % and non-condensing
<1000m**
Less than 70dB @ 1 Meter
INSPIRE 83340-QS
40KVA/40KW
12 V / 9 Ah
250
67

Advertisement