6. Specifications

Tower UPS
MODEL
CAPACITY*
INPUT
Low Line Transfer
Voltage
Range
Low Line Comeback
High Line Transfer
High Line Comeback
Frequency Range
Phase
Power Factor
OUTPUT
Output voltage
AC Voltage Regulation
Frequency Range
Frequency Range (Batt. Mode)
Overload
Current Crest Ratio
Harmonic Distortion
AC Mode to Batt. Mode
Transfer
Time
Inverter to Bypass
Waveform (Batt. Mode)
EFFICIENCY
AC Mode
Battery Mode
BATTERY
Battery Type
Numbers
Standard
Recharge Time
Model
Charging Current
Charging Voltage
Battery Numbers
Long-run
Charging Current
Model*
Charging Voltage
PHYSICAL
Standard
Dimension, D X W X H
Model
Net Weight (kgs)
Dimension, D X W X H
Long-run
Model*
Net Weight (kgs)
ENVIRONMENT
Operation Humidity
Noise Level
MANAGEMENT
Smart RS-232 or USB
Optional SNMP
*Long-run model is only available in 200/208/220/230/240VAC systems.
** Derate capacity to 80% of capacity in Frequency converter mode or when the output voltage is adjusted to 100/200/208VAC.
*** Product specifications are subject to change without further notice.
1K
1000 VA / 800 W
85VAC/75VAC/65VAC/55VAC±5% or 160VAC/140VAC/120VAC/110VAC±5%
( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
95VAC/85VAC/75VAC/65VAC or 175VAC/155VAC/135VAC/125VAC ± 5 %
( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
≧ 0.99 @ nominal voltage (input voltage)
100/110/115/120/127VAC or 200/208/220/230/240VAC
47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized Range)
105%~110%: UPS shuts down after 10 minutes at battery mode or transfer to bypass when
110%~130%: UPS shuts down after 1minute at battery mode or transfer to bypass when the
>130%:UPS shuts down after 3 seconds at battery mode or transfer to bypass when the
≦ 3 % THD (linear load); ≦ 6 % THD (non-linear load)
88%
83%
12 V / 9 AH
2
27.4 VDC ± 1%
2
3
27.4 VDC ±
41.0VDC ±
1%
1%
282 X 145 X 220 (mm)
9.8
282 x 145 x 220 (mm)
4.1
4.1
Supports Windows® 2000/2003/XP/Vista/2008/7/8, Linux, Unix and MAC
Power management from SNMP manager and web browser
2K
2000 VA / 1600 W
(Ambient Temp.<35
(Ambient Temp.<35
145 VAC ± 5 % or 300 VAC ± 5 %
140 VAC ± 5 % or 290 VAC ± 5 %
40Hz ~ 70 Hz
Single phase with ground
±1% (Batt. Mode)
50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
Ambient Temp.<35
the utility is normal
utility is normal
utility is normal
3:1
Zero
4 ms (Typical)
Pure Sinewave
89%
87%
12 V / 9 AH
4
4 hours recover to 90% capacity (Typical)
1.0 A (max.)
54.7 VDC ±1%
4
6
1.0A/2.0A/4.0A/6.0 A
54.7 VDC
82.1VDC
±1%
±1%
397 X 145 X 220 (mm)
17
6.8
6.8
20-90 % RH @ 0- 40°C (non-condensing)
Less than 50dBA @ 1 Meter
22
3000 VA / 2400 W
0
C)
0
C)
0
C
12 V / 9 AH
82.1 VDC ±1%
8
6
109.4VDC
82.1 VDC
±1%
±1%
421 X 190 X 318 (mm)
397x 145 x 220(mm)
6.8
7.4
3K
90%
88%
6
8
109.4VDC
±1%
27.6