8. SPECIFICATIONS

The chapter states the specifications of UPS.

8-1 Conformity And Standards

The UPS has been designed to conform to the European and international standards listed in Table 8-1.
Table 8-1: European and international standards
Item
Uninterruptible power systems (UPS) –Part 1: General and
safety requirements for UPS
Electromagnetic compatibility (EMC) requirements for UPS
Method of specifying the performance and test
requirements of UPS
Notes:
ESD
RS
EFT
Surge
CS
Power-Frequency Magnetic field
Low Frequency Signals
Conduction
Radiation

8-2 Environmental Characteristics

Table 8-2: Environmental characteristics
Item
Noise within 1 m
Altitude
Relative humidity
Operating temperature
Storage and transport
temperature for UPS

8-3 Mechanical Characteristics

Table 8-3: Mechanical characteristics
Model
Rated power (KVA)
Dimensions
D x W x H (mm)
Weight (kg)
Color
IEC/EN 61000-4-2 Level 3
IEC/EN 61000-4-3 Level 3
IEC/EN 61000-4-4 Level 3
IEC/EN 61000-4-5 Level 3
IEC/EN 61000-4-6 Level 3
IEC/EN 61000-4-8 Level 4
IEC/EN 61000-2-2 Level 10V
IEC/EN62040-2 Category C3
IEC/EN62040-2 Category C3
Unit
Specifications
dB
Max. 75
m
≤1000, derate power by 1% per 100m
% RH
0 ~ 95, non-condensing
°C
0 ~ 40°C
°C
-15 ~ 60
PRO833100-QL
PRO833120-QL
100
1000 x 430 x 1200
200
Normative reference
IEC/EN62040-1
IEC/EN62040-2
IEC/EN62040-3
PRO833180-QL
120
200
Black
69
PRO833200-QL
180
200
1000 x 600 x 1200
265
265