6. Specifications

MODEL
CAPACITY*
INPUT
Low Line Transfer
Low Line
Voltage
Comeback
Range
High Line Transfer
High Line
Comeback
Frequency Range
Phase
Power Factor
THDi
OUTPUT
Output voltage
AC Voltage Regulation
Frequency Range
(Synchronized Range)
Frequency Range (Batt.
Mode)
Current Crest Ratio
Harmonic Distortion
AC Mode to Batt.
Transfer
Mode
Time
Inverter to Bypass
Waveform (Batt. Mode)
EFFICIENCY
AC Mode
Battery Mode
BATTERY
Battery Type
Numbers
Standard
Recharge Time
Model
Charging Current
Charging Voltage
Battery Type &
Numbers
Long-run
Charging Current
Model
(max.)
Charging Voltage
PHYSICAL
Dimension, D X W
Standard
X H (mm)
Model
Net Weight (kgs)
Dimension, D X W
Long-run
X H(mm)
Model
Net Weight (kgs)
ENVIRONMENT
Operation Humidity
Noise Level
MANAGEMENT
Smart RS-232 or USB
Optional SNMP
* Derate capacity to 80% of capacity in Frequency converter mode and to 80% when the output voltage is adjusted to 100VAC, 200VAC or
208VAC.
** Product specifications are subject to change without further notice.
PRO801-ES /
PRO8015-ES /
PRO801-EL
PRO8015-EL
1000VA/900W
1500VA/1350W
160VAC/140VAC/120VAC/110VAC ± 5 % or 80VAC/70VAC/60VAC/55VAC ± 5 %
( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
175VAC/155VAC/135VAC/125VAC ± 5 % or 87VAC/77VAC/67VAC/62VAC ± 5 %
THDU < 1.6% @ input and full linear load condition with battery fully charged
200/208/220/230/240VAC or 100/110/115/120/127 VAC
- 2 % THD (Linear Load) ; 4 % THD (Non-linear Load)
90%
90%
89%
89%
12V/7AH
12V/9AH
3
3
4 hours recover to 90% capacity (Typical)
41.0 VDC ± 1%
Depending on the capacity of external batteries
1.0 A/2.0 A/4.0A/6.0 A /8.0 A (Selectable)
41.0 VDC ± 1%
397 X 145 X 220
12
13.8
397 X 145 X 220
6.3
6.5
20-95 % RH @ 0- 40°C (non-condensing)
Less than 50dBA @ 1 Meter (With fan speed control)
Supports Windows® 2000/2003/XP/Vista/2008/7/8, Linux, Unix and MAC
Power management from SNMP manager and web browser
PRO802-ES /
PRO802-EL
2000VA/1800W
300 VAC ± 5 % or 150 VAC ± 5 %
290 VAC ± 5 % or 145 VAC ± 5 %
40Hz ~ 70 Hz
Single phase with ground
- 0.99 @ full load
- 5% @ 205-245VAC or 100~130VAC
± 1% (Batt. Mode)
47 ~ 53 Hz or 57 ~ 63 Hz
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
3:1
Zero
< 4 ms
Pure Sinewave
91%
89%
12V/7AH
6
1.5 A(max.)
82.1 VDC ±1%
82.1 VDC ±1%
22.5
10.5
17
PRO803-ES /
PRO803-EL
3000VA / 2700W
91%
90%
12V/9AH
12V/7AH
6
1.2A(max.)
82.1 VDC ±1% 109.6VDC ± 1%
1A/2A/4A/6A/7A
(Selectable)
82.1 VDC ±1% 109.6VDC ± 1%
421 X 190 X 318
26.6
421 X 190 X 318
11.7
8
32.2