■[F30 Accumulate] Accumulated flow (rate) settings
Set the accumulated flow (rate) function.
<Operation>
Press the UP or DOWN button in function selection mode to select [F30 Accumulate].
Press the UP or DOWN button to select an
item and press the SET button.
Setting of the accumulated-value hold function
Select [Save intvl].
Press the UP or DOWN button
to select an item.
No save: The accumulated flow (rate) is not stored.
2 min: The accumulated flow (rate) is stored at a 2 minute interval.
5 min: The accumulated flow (rate) is stored at a 5 minute interval.
: When using the accumulated value hold function, calculate the product life from the operating conditions, and use the product
within its life.
The maximum access limit of the memory device is approximately 1 million cycles.
•Data stored every 5 minutes: 5 minutes x 1 million times = 5 million minutes = 9.5 years approx.
•Data stored every 2 minutes: 2 minutes x 1 million times = 2 million minutes = 3.8 years approx.
: The value is stored in memory every 2 or 5 minutes.
If the power supply is turned off, the accumulated flow since the last time it was stored will be lost.
: When the power supply is turned on again, the accumulated flow count will start from the last value recorded at B.
Returns to the [F30 Accumulate] accumulated flow (rate) settings.
Press the SET button.
Press the SET button.
-35-
Shifts to the settings of each item.
No.PF※※-OMA1002