Technical Specifications - HMS Networks Intesis IN703DAL0640000 User Manual

Dali-2 protocol translator with serial and ip support - 1 dali channel
Table of Contents

Advertisement

Intesis DALI-2 Protocol Translator with Serial and IP Support - 1 DALI
Channel

5.6. Technical Specifications

Material: Plastic, type PC (UL 94 V-0)
Housing
Color: Light grey (RAL 7035)
Net dimensions: 99 x 88 x 56 mm / 3.89 x 3.46 x 2.20"
Mounting
DIN rail EN 60715 TH35
Cross-section/gauge per terminal:
One core: 0.2 .. 2.5 mm
Wiring
Two cores: 0.2 .. 1.5 mm
Three cores: Not permitted
Use solid wires or stranded wires (twisted or with ferrule).
1 x Green pluggable terminal block (three poles)
24 VDC ±10%, 6.5 W
Power supply
Connect the ground terminal (
1 x Green pluggable terminal block (two poles: A1, A2): Not used
1 x Orange pluggable terminal block (two poles) for DALI:
A3: DA+
A4: DA-
Port A
DALI guaranteed current: 230 mA
DALI maximum current: 250 mA
Voltage rating: 16 VDC
1500 VDC isolation from other ports
Ethernet
1 x Ethernet RJ45 10/100BASE-T
1 x Green pluggable terminal block (three poles):
B1: A+
Port B EIA-485
B2: B-
B3: SG
1500 VDC isolation from other ports (except Port B EIA-232)
Port B EIA-232
1 x DB9 male connector
1500 VDC isolation from other ports (except Port B EIA-485)
USB A type 2.0 connector
USB port
Flash drives only (HDD not supported)
Power consumption limited to 150 mA
Console port
USB Mini-B type 2.0 connector
Type: Manganese Dioxide Lithium button battery
Battery
Size: 20 mm x 3.2 mm (0.79" x 0.13")
Capacity: 3 V, 255 mA
2 x Push buttons
Buttons
Button A
Button B
10 x LEDs for gateway and communication status
2 x Run (Power/Error)
LED indicators
2 x Ethernet Link/Speed
2 x Port A TX/RX
2 x DIP switch blocks for EIA-485 serial port configuration:
DIP switch A (SW A): Not used
DIP switch B (SW B):
Position 1:
DIP switches
On: 120 Ω termination active
SW A / SW B
Off: 120 Ω termination inactive
Position 2 and 3:
On: Polarization active
Off: Polarization inactive
Page 18 of 40
2
(24 .. 11 AWG)
2
(24 .. 15 AWG)
) to the installation grounding
Technical Specifications
2 x Port B TX/RX
1 x Button A indicator
1 x Button B indicator
USER MANUAL Version 1.0.2

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Intesis IN703DAL0640000 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

This manual is also suitable for:

Intesis 700 series

Table of Contents