Intesis DALI-2 Protocol Translator with Serial and IP Support - 1 DALI
Channel
Register name
Update All ECG Status
Ballast Status
Actual Level
Main Device Type
Physical Minimum Level
Min Level
Max Level
Power On Level
System Failure Level
Fade Time
Fade Rate
Arc Power Level
Arc Power Off / On
Dim Down / Up
Recall Min Level
Recall Max Level
Go To Scene
Store Current Level as Scene
Clear/Remove Scene
Add to DALI Group
Remove from DALI Group
Set Fade Time
Set Fade Rate
Set Min Level
Set Max Level
Set Power-on Level
Set System-failure Level
Address formula:
y: Channel number (0)
xx: Ballast short address (0 .. 63)
Page 30 of 40
Possible values
0: Update Finished
1: Trigger Update
b7: PwrCycle
b6: MissShAdd
b5: ResetSt
b4: FadeRun
b3: BallLimErr
b2: LampPwrOn
b1: LampFail
b0: BallFail
0 .. 100%
0: Fluorescent
1: Emergency
6: LED
8: Color control
255: Other
0 .. 100%
0 .. 100%
0 .. 100%
0 .. 100%
0 .. 100%
0 .. 15
1 .. 15
0 .. 100%
0: Off
1: 100%
0: Step Down
1: Step Up
2: Down
3: Up
4: Step Down and Off
5: On and Step Up
1: Recall Min Level
1: Recall Max Level
0 .. 15
0 .. 15
0 .. 15
0 .. 15
0 .. 15
0 .. 15
1 .. 15
0 .. 100%
0 .. 100%
0 .. 100%
0 .. 100%
Address formula
R/W
7000*y+(100*xx)+4
RW
7000*y+(100*xx)+5
R
7000*y+(100*xx)+6
R
7000*y+(100*xx)+7
R
7000*y+(100*xx)+8
R
7000*y+(100*xx)+9
R
7000*y+(100*xx)+10
R
7000*y+(100*xx)+11
R
7000*y+(100*xx)+12
R
7000*y+(100*xx)+13
R
7000*y+(100*xx)+14
R
7000*y+(100*xx)+15
RW
7000*y+(100*xx)+16
RW
7000*y+(100*xx)+17
RW
7000*y+(100*xx)+18
W (T)
7000*y+(100*xx)+19
W (T)
7000*y+(100*xx)+20
RW
7000*y+(100*xx)+21
RW
7000*y+(100*xx)+22
RW
7000*y+(100*xx)+29
RW
7000*y+(100*xx)+30
RW
7000*y+(100*xx)+23
RW
7000*y+(100*xx)+24
RW
7000*y+(100*xx)+25
RW
7000*y+(100*xx)+26
RW
7000*y+(100*xx)+27
RW
7000*y+(100*xx)+28
RW
DALI to Modbus TCP and RTU
USER MANUAL Version 1.0.2
Need help?
Do you have a question about the Intesis IN703DAL0640000 and is the answer not in the manual?