DALI to Modbus TCP and RTU
Table 26. Input devices
Register name
Iyxx_Occupancy Input Value
Iyxx_Light Input Value
Iyxx_Push Buttons-Events
Iyxx_Push Buttons-Button Stuck
Iyxx_Absolute Input
Input Device Comm Error Bit Fields
CH1 (ID 15 - ID 0)
Input Device Cerror Bit Fields
CH1 (ID 31 - ID 16)
Input Device Comm Error Bit Fields
CH1 (ID 47 - ID 32)
Input Device Comm Error Bit Fields
CH1 (ID 63 - ID 48)
Input Device Comm Error Bit Fields
CH2 (ID 15 - ID 0)
Input Device Comm Error Bit Fields
CH2 (ID 31 - ID 16)
Input Device Comm Error Bit Fields
CH2 (ID 47 - ID 32)
Input Device Comm Error Bit Fields
CH2 (ID 63 - ID 48)
Address formula:
y: Line number (0)
x: Input device index (0 .. 63)
z: Instance index (0 .. 9)
SI: Signal index (0 .. 7)
USER MANUAL Version 1.0.2
Possible values
0: Vacant + No Mov
1: Vacant + Mov
2: Occupied + No Mov
3: Occupied + Mov
Lux
As an input value register:
0: Released
1: Pressed
As an event bitfields register:
b0: Button released
b1: Button pressed
b2: Short press
b3: Double press
b4: Long press start
b5: Long press repeat
b6: Long press stop
0: Button free
1: Button stuck
Percent: 0 .. 100%
Absolute value: 0 .. (2^resolution -1)
0: OK
1: Comm error bi
[i=xx-(16*(y-1))]
0: OK
1: Comm error bi
[i=xx-(16*(y-1))]
0: OK
1: Comm error bi
[i=xx-(16*(y-1))]
0: OK
1: Comm error bi
[i=xx-(16*(y-1))]
0: OK
1: Comm error bi
[i=xx-(16*(y-1))]
0: OK
1: Comm error bi
[i=xx-(16*(y-1))]
0: OK
1: Comm error bi
[i=xx-(16*(y-1))]
0: OK
1: Comm error bi
[i=xx-(16*(y-1))]
Intesis DALI-2 Protocol Translator with Serial and IP Support - 1 DALI
Address formula
R/W
14000+(640*y)+(10*x)
R
+z+SI*1280
14000+(640*y)+(10*x)
R
+z+SI*1280
14000+(640*y)+(10*x)
R
+z+SI*1280
14000+(640*y)+(10*x)
R
+z+SI*1280
14000+(640*y)+(10*x)
R
+z+SI*1280
13992
R
13993
R
13994
R
13995
R
13996
R
13997
R
13998
R
13999
R
Channel
Page 39 of 40
Need help?
Do you have a question about the Intesis IN703DAL0640000 and is the answer not in the manual?