6.4.3. Generator side (converter - generator)

Topic
Number of phases
Connection
Number of connections
du/dt
Rated voltage
Insulation U
/ U
0
Rating factor
Maximum length
Single phase current

6.4.4. Braking resistor connection

Topic
Number of phases
Connection
Rated fundamental voltage
Insulation U
/ U
0
Rating factor
Maximum length
NOTE – In some cases, the braking resistor cables are included in the converter delivery.
PRODUCT
PCS6000
Value
1 × 3 (1CL)
2 × 3 (2CL)
2 or 3 / phase
< 2.5
3300
6 / 10
0.85
100
3
Value
2 per resistor
2.8
6 / 10
0.85
6
DOCUMENT KIND
User manual
Unit
Comment
Pfisterer P3PS panel socket
Plugs for up to two cables can be
connected. For more information,
see the project-specific
documentation.
kV
At converter terminals
V
kV
IEEE: 5 / 8 kV
-
To cover converter operation
m
kArms
Maximum 3 s
Unit
Comment
2 resistors per BRU
Pfisterer P3PS panel socket or
cable glands
kV
kV
IEEE: 5 / 8 kV
-
To cover converter operation
m
DOCUMENT ID.
3BHS600000 E40
ELECTRICAL INSTALLATION
REV.
LANG.
PAGE
G
en
72/114