Advertisement

5) Control cabinet door: danger of slight injuries, eg, foot crushing as the door
of the control cabinet is not fixed to the cabinet when the locks are open.
– Support the door with your hand when opening the locks.
– Weight per door: approximately < 20 kg.
6) Generator disconnector: risk of excessive arcing due to undetected arc.
– Risk of injuries from particles, contamination, electric shock, hearing damage,
burns, explosion due to hardware failure, operation beyond specified limits,
unauthorized access
– No access to converter room or platform is allowed when the turbine is idling
with open generator disconnectors or a 2CL converter is running in constricted
operation
– Turbine idling speed shall be limited to a maximum of 30% of rated speed
– 2CL converter must not be operated in constricted mode, except in case of
converter defect that requires disconnecting the defective converter train
– Operation time in constricted mode and idling with open disconnector must
be reduced as far as possible